SERVICE MANUAL KINGSERIES ASH-09AK, ASH-13AK
66666Manual of functions of remote controller and operation methodManual 1 of functions of remote controller6.1.1 Temperature parameterThe room sett
Tpreset +2℃ Tpreset -2℃ Tamb Compressor Outdoor fan Indoor fan Cooling DryStop 6 min. 6 min. 4 min. 4 min. low speed Run Stop 6.1.2.2.3 Protection
3.Other controls1. Memory functionMemory contents: Mode, up and down swing, Light, Setting temp., Setting fan speed, Ordinary settingFahrenheit/Centi
(6) Turbo functionThe turbo function is available in Cool and Heat modes.(7) Dry functionDry function is available in Cool and Dehumidifying modes.(8)
Manual 2 of functions of remote controller1. Temperature parameterThe room setting temperature(Tpreset)The room ambient temperature (Tamb)Basic Functi
DRY ModesWhen Tamb. Tpreset 2 , the unit will run under DRY cooling mode, in which case the compressor and outdoor fan willbe started and the ind
Other controlsTimer functionOrdinary Timer setting:timer on: Under unit off, the timer on function could be set up, if timer on has arrived, controlle
Turbo functionThe turbo function is available in Cool and Heat modes.Dry functionDry function is available in Cool and Dehumidifying modes.Auto fan sp
Dissassembly ProceduresFront Pane(09) Disassembly procedures for indoor unit1. Disassemble the front panel, filterFilterBend the guide louver so that
Operating Procedures / PhotosScrew off the screw, then press the clasps in bytill they loose, then lift up wards the electric cover.4. Disassemble the
Operating Procedures / PhotosScrew off 4 screws fixing the motor cover and thentake the motor cover out.Screw off the holding screw at the left shaft
Open the front panel ,Push the filter upwards tounloose the clasp, and then pull out the two filters.Front Pane(12) Disassembly procedures for indoor
Operating Procedures / PhotosPress the clasps in by till they loose, then lift upwards the electric cover.4. Disassemble the electric cover5. Disassem
Operating Procedures / PhotosScrew off 4 screws fixing the motor cover and thentake the motor cover out.Screw off the holding screw at the left shaft
Push the rotating shaft of front panel outwards tounloose the clasp, and then pull out the front panel.Front Panel(Conventional 09) Disassembly proce
Operating Procedures / PhotosScrew off the screw, then press the clasps in bytill they loose, then lift up wards the electric coverand the light board
Operating Procedures / PhotosScrew off 4 screws fixing the motor cover and thentake the motor cover out.Screw off the holding screw at the left shaft
Front Panel(Conventional 12) Disassembly procedures for indoor unit1. Disassemble the front panel, filterFilterBend the guide louver so that the movab
Operating Procedures / Photos4. Disassemble the Light Board and electric cover6. Disassemble water trayElectric cover5. Disassemble the electric boxLo
Operating Procedures / PhotosScrew off 4 screws fixing the motor cover and thentake the motor cover out.Screw off the holding screw at the left shaft
ModelRemarksASH-09AKASH-13AK1Summary and featuresSummary and features09/13 Outdoor unit:1Ph 220~240V 50HzR410a
(09/12) Disassembly Procedures for Outdoor UnitOperating Procedures / PhotosUnscrew the screw fixing the big handle,and thenremove it downwards to tak
Operating Procedures / PhotosUnscrew the 5 screws fixing the panel anddextrorotate the front panel to pull it out fromgroove.Unscrew the 2 screws fixi
Operating Procedures / PhotosLoosen the fastening nut fixing the axial flow fanwith a spanner, and then take out the nut, springgasket and flap gasket
Operating Procedures / PhotosRespectively unsolder the weld spots of maincapillary and auxiliary capillary to take off thecapillary.10. Disassemble C
99999Failure and analysisThe breaker trips at once when itis set to "ON".Measure insulation resistance to ground to seeif there is any leaka
Improper set of temperatureAdjust set temperatureIf cooling (heating) load isproperCheck the forecasted load of cooling (heating)The refrigerant has l
The indoor fan motor is burned or breaksor has the heat protector malfunction.Replace the fan motor or the defective part.The built-in heat protector
Wrap of refrigerant pipe joint is not closeenough.Re-wrap and make it tight.Water leakageFan of indoor unit contacts other parts. Adjust fan location.
PG motor locked protection H6: Probable reasons:1. Air vents were blocked which may cause the fan speed is too slow;2. Fan blade locked;3. Motor lock
PARTS GUIDEASH-09AK, ASH-13AKKINGSERIES
COOLING HEATING COOLING HEATING2650 /9050 2850/ 9730 3516/12000 4015/13700820 785 1080 11041110 1150 1500 15005.69 5.9 7.6 7.6Model of Indoor UnitFan
Contents 04..…………………………………...ASH-09AK Indoor unit 06..…………………………………………………………………...…ASH-13AK Indo
Explosive view and spare parts list of indoor unit ASH-09AK
Part codeDate 1 Wall-Mounting Frame 01252220 1 2 Rear Case 222020572 1 3 Evaporator Pipe Cover 06122001 1 4 Drainage
Explosive view and spare parts list of indoor unit ASH-13AK
Part codeDate 1 Wall-Mounting Frame 0125221701 1 2 Rear Case 22202451 1 3 Drainage Pipe 05230014 1 4 Cross Flow Fan
Explosive view and spare parts list of outdoor unit ASH-09AK
Part codeDate 1 Front Grill 22413431 1 2 Axial Flow Fan 10333004 1 3 Front Plate 01533012 1 4 Metal Base 012036
Explosive view and spare parts list of outdoor unit ASH-13AK
Part codeDate 1 Front Grill 22413431 1 2 Nut M6 70310131 1 3 Axial Flow Fan 10333004 1 4 Front Plate 01533012 1 5 M
ASH-09AK ASH-13AKHIGHLY GreeASG102CV-B7AT QXA-133uB030Rotary Rotory18A 324.05 5.1875 1160KA-172-LYGN914 B250-150-141E-5
Part namePart nameWall PipeLED displayerRemote control windowGuide louverIndoor unitOutdoor unitFront PanelFilterAir inAir outDrainage hoseAir inAir o
Tube exitAir inletRear ViewRightLeftCeilingWall-Mounting PlateWDHOutline and installation dimensions of indoor unit4Outline and installation dimension
Outline and installation dimensions of outdoor unitUnit:mmASH-09AK, ASH-13AKBoltNutWrenchoveroveroverover
Electrical circuit diagramElectrical circuit diagram55555 ASH-09AKASH-13AK